page 1
page 2
page 3
page 4
page 5
page 6
page 7
page 8
page 9
page 10
page 11
page 12
page 13
page 14
page 15
page 16
page 17
page 18
page 19
page 20
page 21
page 22
page 23
page 24
page 25
page 26
page 27
page 28
page 29
page 30
page 31
page 32
page 33
page 34
page 35
page 36
page 37
page 38
page 39
page 40
page 41
page 42
page 43
page 44
page 45
page 46
page 47
page 48
page 49
page 50
page 51
page 52
page 53
page 54
page 55
page 56
page 57
page 58
page 59
page 60
page 61
page 62
page 63
page 64
page 65
page 66
page 67
page 68
page 69
page 70
page 71
page 72
page 73
page 74
page 75
page 76
page 77
page 78
page 79
page 80
page 81
page 82
page 83
page 84
page 85
page 86
page 87
page 88
page 89
page 90
page 91
page 92
page 93
page 94
page 95
page 96
page 97
page 98
page 99
page 100
page 101
page 102
page 103
page 104
page 105
page 106
page 107
page 108
page 109
page 110
page 111
page 112
page 113
page 114
page 115 page 116
page 117
page 118
page 119
page 120
page 121
page 122
page 123
page 124
page 125
page 126
page 127
page 128
page 129
page 130
page 131
page 132
page 133
page 134
page 135
page 136
page 137
page 138
page 139
page 140
page 141
page 142
page 143
page 144
page 145
page 146
page 147
page 148
page 149
page 150
page 151
page 152
page 153
page 154
page 155
page 156
page 157
page 158
page 159
page 160
page 161
page 162
page 163
page 164
page 165
page 166
page 167
page 168
page 169
page 170
page 171
page 172
page 173
page 174
page 175
page 176
page 177
page 178
page 179
page 180
page 181
page 182
page 183
page 184
page 185
< prev - next > Energy Hydro power civil_works_guidelines_for_micro_hydro (Printable PDF)
CIVIL WORKS GUIDELINES FOR MICRO-HYDROPOWER IN NEPAL
113
Figure 7.5 Distances and angles used in anchor block and support pier equation
7.4.2 DESCRIPTION OF FORCES
F1 - F1 is the component of the weight of pipe and enclosed
water perpendicular to the pipe alignment. If there is a bend
at the anchor, however, both the upstream and downstream
lengths of pipe contribute separately, each force perpendicular
to the centreline of the pipe segment which contributes to it.
F2-F2 is the frictional force of pipe on support piers. If the
penstock moves longitudinally over support piers, a friction
force on the pipe is created at each pier. A force “F2”, equal to
the sum of all these forces but opposite in direction, acts on
the anchor. This force exists only where one or more support
piers are located between the anchor block and an expansion
joint. For example, if an expansion joint is located immediately
downhill of the anchor, friction forces on the downhill length
of pipe will not be transmitted to the anchor block from that
side. The friction coefficient, f, depends on the material
against which the penstock slides and is as follows:
steel on concrete, f = 0.60
steel on steel, rusty plates, f = 0.50
steel on steel, greased plates or tar paper in between, f = 0.25
F3 - F3 is the force due to hydrostatic pressure within a bend.
The hydrostatic pressure at a bend creates a force which acts
outward for upward bends and inward if the bend is down-
ward. This is a major force which must be considered in
designing anchor blocks. However, the block size can be
significantly reduced if the bend angle (β - α) can be
minimised while fixing the penstock alignment.
F4 - F4 is the force due to the component of the weight of pipe
parallel to the pipe alignment. On a slope, the component of
the weight of the pipe which is parallel to the pipe tends to
pull it downhill and exerts a force on an anchor block. The
sections of pipe both upstream and downstream of an anchor
block may have to be considered. The lengths ‘L4u’ and ‘L4d’ in
the equation for the force “F4” acting on an anchor block are
the lengths of the upstream or downstream section of the
penstock which is actually to be held by that block. The
upstream section may begin at the forebay or, more usually, at
an expansion joint. The downstream section usually ends at
an expansion joint. If the expansion joint downstream of an
anchor block is located near the anchor, as it usually is, the
force arising from the weight of the downhill section of pipe
between the anchor and the joint is insignificant and is
usually neglected. Also, the anchor block will not experience
this force if the penstock is buried since the ground friction
will resist this force.
F5 - F5 is the force that is transmitted to the anchor block due
to thermally induced stresses in the absence of an expansion
joint. If an exposed section of a rigid pipe does not incorporate
an expansion joint, thermally induced stresses build up in
the pipe and act on the anchor block. The associated force
“F5” may push against the anchor block (with increasing
temperature) or pull the anchor block (with decreasing
temperature).
F6 - F6 is the force due to friction within the expansion joint.
To prevent leaking, the packing within an expansion joint
must be tightened sufficiently. However, this tightening also
makes it more difficult for the joint to accept any longitudinal
movement of the pipe. Friction between the packing and the
concentric sleeves in the expansion joint creates a force “F6
which opposes any expansion or contraction of the pipe. This
force is dependent on pipe diameter, tightness of the packing